Friday, June 29, 2007

AIR CHANGES PER HOUR CALCULATOR

Table 1:
Recommended Air Velocity Rates
Class
Iso 146144-1
(Standard 209E)
Average Airflow Velocity Air Changes
Per Hour
ISO 8 (Class 100,000) 0.005 - 0.041 m/sec (1 - 8 ft/min) 5 - 48
ISO 7 (Class 10,000) 0.051 - 0.076 m/sec (10 - 15 ft/min) 60 - 90
ISO 6 (Class 1,000) 0.127 - 0.203 m/sec (25 - 40 ft/min) 150 - 240
ISO 5 (Class 100) 0.203 - 0.406 m/sec (40 - 80 ft/min) 240 - 480
ISO 4 (Class 10) 0.254 - 0.457 m/sec (50 - 90 ft/min) 300 - 540
ISO 3 (Class 1) 0.305 - 0.457 m/sec (60 - 90 ft/min) 360 - 540
ISO 1-2 0.305 - 0.508 m/sec (60 - 100 ft/min) 360 - 600
Note: Actual average velocity and air changes required may vary depending
on
the application and floor plan. Source: Institute of Environmental Science
Table 2:
Recommended Ceiling Filter Coverage
Class Ceiling Coverage
ISO 8 (Class 100,000) 5 - 15%
ISO 7 (Class 10,000) 15 - 20%
ISO 6 (Class 1,000) 25 - 40%
ISO 5 (Class 100) 35 - 70%
ISO 4 (Class 10) 50 - 90%
ISO 3 (Class 1) 60 - 100%*
ISO 1-2 80 - 100%*
Note: Actual average velocity and air changes required may vary
depending on the application and floor plan.

* ULPA filters required in Class 1/10 applications. HEPA filters
required for all others.

AIR CHANGES PER HOUR CALCULATOR

Calculation of air volume
The volume of air required to operate a
ventilating and cooling system is a
very fundamental requirement. Before

air volume is estimated or calculated, careful consideration should be given to the following factors.

The objectives of the ventilation system
Be sure that the decision you make will accomplish the most important objectives or will overcome the most important problems. This should be the overriding consideration in the selection of a system of ventilation.

The budget
Availability of money to finance the system is a factor that must be considered early in the planning stage. The funds available will affect the objectives you set and will influence the system of ventilation selected to meet the objectives.

Alternate methods of
calculating the required air volume
The method selected for calculating air volume will relate closely to the objectives to be accomplished by the system. Based on the objectives and funds available, you can now consider the alternatives and select the best method to use in calculating air volume requirements. A description of these methods follows.

Rate of air change method
This is a time-honored approach to a determination of air volume requirements. It is based on the theory that a complete change of air in a room or building should be made at a certain time frequency. The rate selected is frequently an arbitrary decision. It may be based on experience with similar installations or may be established by a health or safety code. Many fan manufacturers have published charts that show recommended rates of air change for typical installations.
The formula for calculating the air volume in CFM by the rate of air change method is as follows:


Typical layout of fans for rate of air change
method

Although the rate of air change

method of calculating air volume has

been used for many years, American

Coolair engineers have found it

unsatisfactory except in relatively

small buildings or rooms. For jobs

that involve personnel comfort.

this method is not recommended

if the building is over 50,000 cubic

feet in content or more than l00' in

length.

CFM per square foot of

floor area method
This method of calculation is a modern

adaptation of the rate of air change

formula. Total air volume (cubic feet

per minute) is determined by

multiplying the total square feet

of floor area by an arbitrary CFM per

square foot figure. The figure selected

may be as low as 2 CFM or as high

as 12 CFM per square foot. Four

CFM per square foot has been recom

mended as a minimum for summer

ventilation of large assembly type

operations.
This method of calculation, like

the rate of air change method, is

likely to produce unsatisfactory

results in many cases. Failure to

control air distribution and air velocity

can be a major weakness in the whole

concept. Selection of a CFM per square

foot figure should be based on

experience and a proven method

of air distribution.

Rate of air velocity

method
This method of calculating air volume

needed for a system is highly

recommended by American Coolair.

A breeze conditioning system

can be highly effective in providing

personnel comfort in hot weather

if the recommendations outlined

below are observed. It has been

determined from field experience

that an average air velocity of 150

feet per minute (FPM) to 200 FPM

is usually sufficient for personnel

cooling under summertime

conditions. The CFM required to

do the job is calculated by multiplying

the cross section of an area through

which the air is to move by the desired

velocity. This is expressed in the

following formula.


Air velocity method of determining CFM

CFM =
(cu. ft./min.)
Area to be cooled (cubic feet)*

Recommended rate of air change (minutes)
* Area to be cooled (cu. ft.) = Length (ft.) x Width (ft.) x Average Ceiling Height (ft.)

Example: A laundry 100' long by 30' wide with a 15' ceiling height requires a complete air change each 1/2 minute. The necessary air volume (fan capacity) is de determined from the above formula as follows:

CFM = 100 x 30 x 15 = 90,000 cu. ft. / min.

How to calculate air change rates

How to calculate air change rates - air

change rate equations in imperial

and SI units


air change rate

Air Change Rate - Imperial Units

Air change rate per hour can be expressed in imperial Units as

n = 60 Q / V (1)

where

r = air change rate per hour

Q = fresh air flow through the room (Cubic Feet per Minute (cfm))

V = volume of the room (Cubic Feet)

Air Change Rate - SI Units

Air change rate expressed in SI-units:

n = 3600 Q / V (2)

where

r = air change rate per hour

Q = fresh air flow through the room (m3/s)

V = volume of the room (m3)

Example - Air Change Rate SI Units

With an air flow of 3 m3/s in a 20000 m3 room the air flow rate can

be calculated as

n = 3600 3 (m3/s) / 20000 (m3)

= 0.54

No comments: